HYW-13 M5

On-Site Power / HI RANGE

HYW-13 M5

Open Skid

Prime power11.4 kVA
Standby power12.3 kVA

TECHNICAL DATA

Specifications

Model code
G-90-6-5-3
Engine
YANMAR
Alternator
STAMFORD
Fuel
Diesel
Frequency
50 Hz
Phase
Single phase
Emissions
non certified
Version
Open Skid
Prime power
9.1 kW
Standby power
10 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
230 V (m) 50 Hz Single phase STAMFORD

INCLUDED

Equipment

Engine

Engine Specifications 1.500 r.p.m. Rated Engine Output: 12,2kW prp ; 13,2kW standby Manufacturer: YANMAR Model: 3TNV88BGGEH Engine Type: 4-stroke diesel Injection Type: Direct Aspiration Type: Natural Number of cylinders and arrangement: 3-L Bore and Stroke: 88 x 90 mm Displacement: 1,642 L Cooling System: Coolant Lube Oil Specifications: SAE 3 class 10W30 / API grade CD,CF Compression Ratio: 19,1 Fuel Consumption ESP: 3,51 l/h Fuel Consumption 100% PRP: 3,19 l/h Fuel Consumption 75 % PRP: 2,50 l/h Fuel Consumption 50 % PRP: 1,83 l/h Lube oil consumption with full load: 0,27 Total oil capacity: 6,7 L Total coolant capacity: 4,8 L Governor Type Mechanical Air Filter Type Dry Inner diameter exhaust pipe: 36 mm Diesel engine 4-stroke cycle Water-cooled 12V electrical system Water separator filter (visible level) Dry air filter Radiator with pusher fan Hot parts protection Moving parts protection

Alternator

Generator: STAMFORD Model: PI044H Poles: 4 Connection type (standard): Series Mounting type: S-4 7,5" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation) Generator: STAMFORD Model: S0L2.G1 Poles: 4 Connection type (standard): Double delta Mounting type: S-4 7,5" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Chassis with integrated fuel tank Fuel level gauge Fuel tank drain plug Steel industrial silencer -15db(A) attenuation Fuel transfer pump (Optional) Steel residential silencer -35db(A) attenuation. (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) - EXHAUST SYSTEM. Maximum exhaust temperature: 450 ºC Exhaust Gas Flow: 3,07 m3/min Maximum allowed back pressure: 1300 mm H2o - NECESSARY AMOUNT OF AIR. Intake air flow: 66,5 m3/h Cooling Air Flow: 0,7 m3/s Alternator fan air flow: 0,105 m3/s - STARTING SYSTEM. Starting power: 1,2 kW Starting power: 1,63 CV Recommended battery: 66 Ah Auxiliary Voltage: 12 Vdc - FUEL SYSTEM Fuel Oil Specifications: Diesel Fuel Tank: 60 L

Dimensions

- DIMENSIONS. Length: 1.450 mm Height: 1.286 mm Width: 620 mm Maximum shipping volume: 1,16 m3 Weight with liquids in radiator and sump: 369 kg Fuel tank capacity: 60 L Autonomy: 24 Hours