Engine
Engine Specifications 1.800 r.p.m.
Rated Engine Output: 350kW cop
Manufacturer: GUASCOR
Model: G.18SL
Engine Type: 4-stroke Otto Cycle
Injection Type: Carburization
Aspiration Type: Turbocharged
Number of cylinders and arrangement: 6-L
Bore and Stroke: 152 x 165 mm
Displacement: 18 L
Cooling System: Water + Antifreeze
Lube Oil Specifications: SAE 40
Compression Ratio: 11,6
Fuel Consumption 100% PRP: 904 kW
Fuel Consumption 80 % PRP: 753 kW
Fuel Consumption 75 % PRP: 717,29 kW
Fuel Consumption 50 % PRP: 530,8 kW
Fuel Consumption 25 % PRP: 344,3 kW
Lube oil consumption with full load: 0,35
Total oil capacity including tubes, filters 86 L
Governor Type Electrical
Air Filter Type Semi-humid
Biogas Engine
4-stroke cycle
Water-cooled
Radiator with pusher fan
HTW sender
LOP sender
Hot parts protection
Alternator
Generator: STAMFORD
Model: S4L1S.F
Poles: 4
Connection type (standard): Star-series
Mounting type: S-0 18''
Insulation: H class
Enclosure (according IEC-34-5): IP23
Exciter system: Self-excited, brushless
Voltage regulator: A.V.R. (Electronic)
Bracket type: Double drive-shaft
Coupling system: Elastic Coupling
Coating type: Standard (Vacuum impregnation)
Version
- OPEN SET VERSION.
Emergency stop button
Steel chassis
Steel industrial silencer -15db(A) attenuation
Steel residential silencer -35db(A) attenuation.
- GAS RAMP.
Manual shut-off valve
Double solenoid valve
High pressure regulator
Primary pressure regulator
Secondary pressure regulator (Zero pressure regulator)
Low pressure switch
High pressure switch
Valve (tightness) testing system
Inlet pressure manometer
Outlet pressure manometer
Special Start/Stop sequence
Installation
- ELECTRICAL SYSTEM.
Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
Battery Switch
Adjustable earth leakage protection (time & sensitivity) standard in M12, with thermal magnetic protection
Battery charger (standard on gensets with automatic control panels)
Heating resistor (standard on sets with automatic control panels)
Battery charger alternator with ground connection
Starter battery/ies installed (cables and bracket included)
Ground connection electrical installation with connection ready for ground spike (not supplied)
- EXHAUST SYSTEM.
Maximum exhaust temperature: 399 ºC
Exhaust Gas Flow: 0,533 kg/s
Maximum allowed back pressure: 450 mm H2o
- NECESSARY AMOUNT OF AIR.
Cooling Air Flow: 12,25 m3/s
Alternator fan air flow: 0,99 m3/s
- STARTING SYSTEM.
Auxiliary Voltage: 12 Vdc
- FUEL SYSTEM
Fuel Oil Specifications: Biogas