HGP-545 T6 LPG

On-Site Power / HI RANGE

HGP-545 T6 LPG

Open Skid

Prime power572 kVA
Standby power639 kVA

TECHNICAL DATA

Specifications

Model code
G-1891-11-1-3
Engine
PSI
Alternator
STAMFORD
Fuel
LPG
Frequency
60 Hz
Phase
Three phase
Emissions
Cumple EPA
Version
Open Skid
Prime power
458 kW
Standby power
511 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
416/240 V 60 Hz Three phase STAMFORD
480/277 V 60 Hz Three phase STAMFORD
208/120 V 60 Hz Three phase STAMFORD
220/127 V 60 Hz Three phase STAMFORD
440/254 V 60 Hz Three phase STAMFORD
460/265 V 60 Hz Three phase STAMFORD
600/347 V 60 Hz Three phase STAMFORD

INCLUDED

Equipment

Engine

Engine Specifications 1.800 r.p.m. Rated Engine Output: 486kW prp ; 544kW standby Manufacturer: PSI Model: 40L Engine Type: 4-stroke Otto Cycle Injection Type: Direct Aspiration Type: Turbocharged and after-cooled Number of cylinders and arrangement: 12-V Bore and Stroke: 150 x 185 mm Displacement: 39,2 L Cooling System: Coolant Lube Oil Specifications: SAE 15W40; API CD or CE Compression Ratio: 10,5:1 Fuel Consumption ESP: 2107 kW Fuel Consumption 100% PRP: 1816 kW Fuel Consumption 80 % PRP: 1334 kW Fuel Consumption 50 % PRP: 938 kW Fuel Consumption 25 % PRP: 625 kW Total oil capacity: 146 L Total coolant capacity: 172 L Governor Type Electrical Air Filter Type Dry LPG-liquefied petrol gas engine 4-stroke cycle Water-cooled Radiator with pusher fan (vertical configuration) HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: STAMFORD Model: S5L1S.C4 Poles: 4 Connection type (standard): Star-series Mounting type: S-0 18'' Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Double drive-shaft Coupling system: Elastic Coupling Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Emergency stop button Steel chassis Anti-vibration shock absorbers Steel industrial silencer -15db(A) attenuation Steel residential silencer -35db(A) attenuation. - GAS RAMP. Manual shut-off valve Gas filter Double solenoid valve High pressure regulator Primary pressure regulator Low pressure switch High pressure switch Valve (tightness) testing system Inlet pressure manometer Outlet pressure manometer Special Start/Stop sequence

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Battery Switch Adjustable earth leakage protection (time & sensitivity) standard in M12, with thermal magnetic protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) - EXHAUST SYSTEM. Maximum exhaust temperature: 700 ºC Exhaust Gas Flow: 107 m3/min Maximum allowed back pressure: 13 kPa - NECESSARY AMOUNT OF AIR. Intake air flow: 2040 m3/h Alternator fan air flow: 1,312 m3/s - STARTING SYSTEM. Starting power: 10 kW Starting power: 13,6 CV Recommended battery: 75 x 4 Ah Auxiliary Voltage: 24 Vdc - FUEL SYSTEM Fuel Oil Specifications: LPG

Dimensions

- DIMENSIONS. Length: 4.500 mm Height: 2.400 mm Width: 2.200 mm Maximum shipping volume: 23,76 m3