HGP-165 T6 NG

On-Site Power / HI RANGE

HGP-165 T6 NG

Open Skid

Prime power168 kVA
Standby power197 kVA

TECHNICAL DATA

Specifications

Model code
G-974-9-4-3
Engine
PSI
Alternator
MECC ALTE
Fuel
Natural Gas
Frequency
60 Hz
Phase
Three phase
Emissions
Cumple EPA
Version
Open Skid
Prime power
134 kW
Standby power
158 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
380/220 V 60 Hz Three phase MECC ALTE
416/240 V 60 Hz Three phase MECC ALTE
480/277 V 60 Hz Three phase MECC ALTE
208/120 V 60 Hz Three phase MECC ALTE
220/127 V 60 Hz Three phase MECC ALTE
440/254 V 60 Hz Three phase MECC ALTE
600/347 V 60 Hz Three phase MECC ALTE

INCLUDED

Equipment

Engine

Engine Specifications 1.800 r.p.m. Rated Engine Output: 143,3kW prp ; 169,3kW standby Manufacturer: PSI Model: 8.1LT Engine Type: 4-stroke Otto Cycle Injection Type: Carburization Aspiration Type: Turbocharged and after-cooled Number of cylinders and arrangement: 6-L Bore and Stroke: 111 x 139 mm Displacement: 8,1 L Cooling System: Coolant Lube Oil Specifications: API CD/≥CF, SAE 15W40 Compression Ratio: 10,5 : 1 Fuel Consumption ESP: 1.772.56 cfh Fuel Consumption 100% PRP: 1.535.99 cfh Fuel Consumption 75 % PRP: 1.214.66 cfh Fuel Consumption 50 % PRP: 875.69 cfh Fuel Consumption 25 % PRP: 529.65 cfh Total oil capacity including tubes, filters 27,5 L Total coolant capacity: 80 L Governor Type Electrical Air Filter Type Dry Natural Gas engine 4-stroke cycle Water-cooled 24V electrical system Dry air filter Radiator with pusher fan HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: MECC ALTE Model: ECP34.1L4C Poles: 4 Connection type (standard): Star-series Mounting type: S-2 11,5" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-regulated brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Steel industrial silencer -15db(A) attenuation Steel residential silencer -35db(A) attenuation. (Optional) - GAS RAMP. Manual shut-off valve Gas filter Double solenoid valve Primary pressure regulator Secondary pressure regulator (Zero pressure regulator) Low pressure switch Valve (tightness) testing system Inlet pressure manometer Outlet pressure manometer Special Start/Stop sequence High pressure regulator (Optional) High pressure switch (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) - EXHAUST SYSTEM. Maximum exhaust temperature: 750 ºC Exhaust Gas Flow: 31,9 m3/min Maximum allowed back pressure: 10,2 kPa - NECESSARY AMOUNT OF AIR. Intake air flow: 600 m3/h Alternator fan air flow: 0,573 m3/s - STARTING SYSTEM. Starting power: 4,5 kW Starting power: 6,12 CV Recommended battery: 150 Ah Auxiliary Voltage: 24 Vdc - FUEL SYSTEM Fuel Oil Specifications: Natural Gas

Dimensions

- DIMENSIONS. Length: 3.000 mm Height: 1.621 mm Width: 1.160 mm Maximum shipping volume: 5,64 m3 Weight with liquids in radiator and sump: 2.165 kg