HGO-25 M5 NG

On-Site Power / HI RANGE

HGO-25 M5 NG

Soundproof

Prime power23 kVA
Standby power25 kVA

TECHNICAL DATA

Specifications

Model code
G-1180-6-4-4
Engine
FORD
Alternator
STAMFORD
Fuel
Natural Gas
Frequency
50 Hz
Phase
Single phase
Emissions
non certified
Version
Soundproof
Prime power
18.1 kW
Standby power
19.8 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
230 V (m) 50 Hz Single phase STAMFORD

INCLUDED

Equipment

Engine

Engine Specifications 1.500 r.p.m. Rated Engine Output: 22,6kW prp ; 24,8kW standby Manufacturer: FORD Model: MSG425 Engine Type: 4-stroke Otto Cycle Injection Type: Carburization Aspiration Type: Natural Number of cylinders and arrangement: 4-L Bore and Stroke: 89 x 100 mm Displacement: 2,5 L Cooling System: Coolant Lube Oil Specifications: API SJ/SH, SAE 5W-20 Compression Ratio: 9,7:1 Fuel Consumption 100% PRP: 254.23 cfh Total oil capacity including tubes, filters 6,3 L Governor Type Electrical Air Filter Type Dry Natural Gas engine 4-stroke cycle Water-cooled 12V electrical system Dry air filter Radiator with pusher fan HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: STAMFORD Model: S1L2.N1 Poles: 4 Connection type (standard): Double delta Mounting type: S-4 10" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- SOUNDPROOFED VERSION. Steel chassis Anti-vibration shock absorbers External emergency stop switch Bodywork made from high quality steel plate High mechanical strength Low noise emissions level Soundproofing provided by high-density volcanic rock wool Epoxy polyester powder coating Full access for maintenance (water, oil and filters, no need to remove the canopy) Reinforced lifting hooks for crane hoisting Chassis drain plug Steel residential silencer -35db(A) attenuation. IP Protection according to ISO 8528-13:2016 - GAS RAMP. Gas filter Double solenoid valve High pressure regulator Primary pressure regulator Low pressure switch Inlet pressure manometer Outlet pressure manometer Special Start/Stop sequence High pressure switch (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) - EXHAUST SYSTEM. Exhaust Gas Flow: 4,9 m3/min Maximum allowed back pressure: 20,32 kPa Exhaust Flange Size (external diameter): 65 mm - NECESSARY AMOUNT OF AIR. Intake air flow: 297,3 m3/h Cooling Air Flow: 1,2 m3/s Alternator fan air flow: 0,176 m3/s - STARTING SYSTEM. Recommended battery: 95 Ah Auxiliary Voltage: 12 Vdc - FUEL SYSTEM Fuel Oil Specifications: Natural Gas

Dimensions

- DIMENSIONS. Length: 2.100 mm Height: 1.350 mm Width: 975 mm Maximum shipping volume: 2,76 m3 Weight with liquids in radiator and sump: 1.025 kg Sound pressure level: 68 ± 2,4 dB(A)@7m