HGO-100 T6 LPG

On-Site Power / HI RANGE

HGO-100 T6 LPG

Open Skid

Prime power97 kVA
Standby power107 kVA

TECHNICAL DATA

Specifications

Model code
G-1937-9-2-3
Engine
FORD
Alternator
MECC ALTE
Fuel
LPG
Frequency
60 Hz
Phase
Three phase
Emissions
non certified
Version
Open Skid
Prime power
77 kW
Standby power
86 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
380/220 V 60 Hz Three phase MECC ALTE
416/240 V 60 Hz Three phase MECC ALTE
480/277 V 60 Hz Three phase MECC ALTE
220/127 V 60 Hz Three phase MECC ALTE
440/254 V 60 Hz Three phase MECC ALTE

INCLUDED

Equipment

Engine

Engine Specifications 1.800 r.p.m. Rated Engine Output: 85kW prp ; 95kW standby Manufacturer: FORD Model: WSG873 Engine Type: 4-stroke Otto Cycle Injection Type: Carburization Aspiration Type: Natural Number of cylinders and arrangement: 8-V Bore and Stroke: 107,2 x 101 mm Displacement: 7,3 L Cooling System: Liquid (water + 50% glycol) Lube Oil Specifications: API ≥SM, SAE 5W30 Compression Ratio: 10,5 Total oil capacity including tubes, filters 7,5 L Governor Type Electrical Air Filter Type Dry LPG-liquefied petrol gas engine 4-stroke cycle Water-cooled 12V electrical system Dry air filter Radiator with pusher fan HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: MECC ALTE Model: ECP32.2L4C Poles: 4 Connection type (standard): Star-series Mounting type: S-3 11"1/2 Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Steel industrial silencer -15db(A) attenuation Steel residential silencer -35db(A) attenuation. (Optional) - GAS RAMP. Gas filter Double solenoid valve Low pressure switch High pressure switch Inlet pressure manometer Outlet pressure manometer Special Start/Stop sequence High pressure regulator (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Battery Switch Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) - EXHAUST SYSTEM. Exhaust Gas Flow: 17 m3/min Maximum allowed back pressure: 20,32 kPa - NECESSARY AMOUNT OF AIR. Intake air flow: 335,07 m3/h Alternator fan air flow: 0,308 m3/s - STARTING SYSTEM. - FUEL SYSTEM Fuel Oil Specifications: LPG

Dimensions

- DIMENSIONS. Length: 2.100 mm Height: 1.650 mm Width: 900 mm Maximum shipping volume: 3,12 m3 Weight with liquids in radiator and sump: 1.043 kg