HIMOINSA

On-Site Power / HI RANGE

HDW-815 T5

Open Skid

Prime power812 kVA
Standby power910 kVA

TECHNICAL DATA

Specifications

Model code
G-1786-10-1-3
Engine
HYUNDAI
Alternator
STAMFORD
Fuel
Diesel
Frequency
50 Hz
Phase
Three phase
Emissions
non certified
Version
Open Skid
Prime power
650 kW
Standby power
728 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
400/230 V 50 Hz Three phase STAMFORD

INCLUDED

Equipment

Engine

Engine Specifications 1.500 r.p.m. Rated Engine Output: 684kW prp ; 769kW standby Manufacturer: HYUNDAI Model: DP222CB Engine Type: 4-stroke diesel Injection Type: Direct Aspiration Type: Turbocharged and after-cooled Number of cylinders and arrangement: 12-V Bore and Stroke: 128 x 142 mm Displacement: 21,927 L Cooling System: Coolant Lube Oil Specifications: 10W-40 (API CJ-4, CK-4) Compression Ratio: 14,6:1 Fuel Consumption ESP: 130 l/h Fuel Consumption 100% PRP: 168 l/h Fuel Consumption 75 % PRP: 127 l/h Fuel Consumption 50 % PRP: 93 l/h Fuel Consumption 25 % PRP: 50 l/h Total oil capacity including tubes, filters 78 L Total coolant capacity: 66 L Governor Type Electrical Air Filter Type Dry Oil temperature sensor Low coolant level sensor Exhaust gas compensator Diesel engine 4-stroke cycle Water-cooled 24V electrical system Standard air filter Standard fuel filter Standard oil filter Radiator with pusher fan Radiator water level sensor HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: STAMFORD Model: S6L1D.D4 Poles: 4 Connection type (standard): Star-series Mounting type: S-0 18'' Insulation: H class Enclosure (according IEC-34-5): IP23 Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Chassis with integrated fuel tank Fuel level gauge Fuel tank drain plug Fuel transfer pump (Optional) Steel industrial silencer -15db(A) attenuation (Optional) Steel residential silencer -35db(A) attenuation. (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Connection panel wired to the safety protection (open thermal magnetic protection and alarm) Maintenance-free and anti-explosion battery Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) - EXHAUST SYSTEM. Maximum exhaust temperature: 525 ºC Exhaust Gas Flow: 136 m3/min Maximum allowed back pressure: 5,9 kPa - NECESSARY AMOUNT OF AIR. Cooling Air Flow: 21,1 m3/s Alternator fan air flow: 1,42 m3/s - STARTING SYSTEM. Starting power: 7 kW Starting power: 9,52 CV Recommended battery: 75 x 4 Ah Auxiliary Voltage: 24 Vdc - FUEL SYSTEM Fuel Oil Specifications: Diesel Fuel Tank: 400 L

Dimensions

- DIMENSIONS. Length With Control Panel: 3.800 mm Height: 2.200 mm Width: 1.950 mm Weight with liquids in radiator and sump: 5.435 kg Fuel tank capacity: 400 L Autonomy: 3 Hours