HIMOINSA

On-Site Power / HI RANGE

HDW-750 T5

Open Skid

Prime power753 kVA
Standby power830 kVA

TECHNICAL DATA

Specifications

Model code
G-964-7-3-3
Engine
HYUNDAI
Alternator
MECC ALTE
Fuel
Diesel
Frequency
50 Hz
Phase
Three phase
Emissions
non certified
Version
Open Skid
Prime power
602 kW
Standby power
664 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
400/230 V 50 Hz Three phase MECC ALTE
200/115 V 50 Hz Three phase MECC ALTE
380/220 V 50 Hz Three phase MECC ALTE
230 V (t) 50 Hz Three phase MECC ALTE

INCLUDED

Equipment

Engine

Engine Specifications 1.500 r.p.m. Rated Engine Output: 633kW prp ; 699kW standby Manufacturer: HYUNDAI Model: DP222LCF Engine Type: 4-stroke diesel Injection Type: Direct Aspiration Type: Turbocharged and after-cooled Number of cylinders and arrangement: 12-V Bore and Stroke: 128 x 142 mm Displacement: 21,927 L Cooling System: Coolant Lube Oil Specifications: API CH4 SAE 15W40 or 10W40 Compression Ratio: 15:1 Fuel Consumption ESP: 172,8 l/h Fuel Consumption 100% PRP: 161 l/h Fuel Consumption 75 % PRP: 119,1 l/h Fuel Consumption 50 % PRP: 79,3 l/h Fuel Consumption 25 % PRP: 42,1 l/h Lube oil consumption with full load: 0,5 % of fuel consumption Total oil capacity: 40 L Total coolant capacity: 114 L Governor Type Electrical Air Filter Type Dry Diesel engine 4-stroke cycle Water-cooled 24V electrical system Water separator filter (no visible level) Dry air filter Radiator with pusher fan HTW sender LOP sender Hot parts protection Moving parts protection Radiator water level sensor (Optional)

Alternator

Generator: MECC ALTE Model: ECO40.VL4C Poles: 4 Connection type (standard): Star-series Mounting type: S-1 14" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Chassis with integrated fuel tank Fuel level gauge Fuel tank drain plug Steel industrial silencer -15db(A) attenuation Fuel transfer pump (Optional) Steel residential silencer -35db(A) attenuation. (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) - EXHAUST SYSTEM. Maximum exhaust temperature: 502 ºC Exhaust Gas Flow: 108 m3/min Maximum allowed back pressure: 5,9 kPa - NECESSARY AMOUNT OF AIR. Intake air flow: 2700 m3/h Cooling Air Flow: 14,33 m3/s Alternator fan air flow: 0,9 m3/s - STARTING SYSTEM. Starting power: 7 kW Starting power: 9,52 CV Recommended battery: 200 x 2 Ah Auxiliary Voltage: 24 Vdc - FUEL SYSTEM Fuel Oil Specifications: Diesel Maximum power suction pump: 225 mm Hg Maximum return feed pump: 450 mm Hg Fuel Tank: 875 L

Dimensions

- DIMENSIONS. Length: 4.200 mm Height: 2.310 mm Width: 1.600 mm Maximum shipping volume: 15,52 m3 Weight with liquids in radiator and sump: 4.774 kg Fuel tank capacity: 875 L Autonomy: 7 Hours