Engine
Engine Specifications 1.500 r.p.m.
Rated Engine Output: 633kW prp ; 699kW standby
Manufacturer: HYUNDAI
Model: DP222LCF
Engine Type: 4-stroke diesel
Injection Type: Direct
Aspiration Type: Turbocharged and after-cooled
Number of cylinders and arrangement: 12-V
Bore and Stroke: 128 x 142 mm
Displacement: 21,927 L
Cooling System: Coolant
Lube Oil Specifications: API CH4 SAE 15W40 or 10W40
Compression Ratio: 15:1
Fuel Consumption ESP: 172,8 l/h
Fuel Consumption 100% PRP: 161 l/h
Fuel Consumption 75 % PRP: 119,1 l/h
Fuel Consumption 50 % PRP: 79,3 l/h
Fuel Consumption 25 % PRP: 42,1 l/h
Lube oil consumption with full load: 0,5 % of fuel consumption
Total oil capacity: 40 L
Total coolant capacity: 114 L
Governor Type Electrical
Air Filter Type Dry
Diesel engine
4-stroke cycle
Water-cooled
24V electrical system
Water separator filter (no visible level)
Dry air filter
Radiator with pusher fan
HTW sender
LOP sender
Hot parts protection
Moving parts protection
Radiator water level sensor (Optional)
Alternator
Generator: STAMFORD
Model: S6L1D.C4
Poles: 4
Connection type (standard): Star-series
Mounting type: S-1 14"
Insulation: H class
Enclosure (according IEC-34-5): IP23
Voltage regulator: A.V.R. (Electronic)
Bracket type: Single bearing
Coupling system: Flexible disc
Coating type: Standard (Vacuum impregnation)
Version
- OPEN SET VERSION.
Steel chassis
Emergency stop button
Anti-vibration shock absorbers
Chassis with integrated fuel tank
Fuel level gauge
Fuel tank drain plug
Steel industrial silencer -15db(A) attenuation
Fuel transfer pump (Optional)
Steel residential silencer -35db(A) attenuation. (Optional)
Installation
- ELECTRICAL SYSTEM.
Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
Battery charger (standard on gensets with automatic control panels)
Heating resistor (standard on sets with automatic control panels)
Battery charger alternator with ground connection
Starter battery/ies installed (cables and bracket included)
Ground connection electrical installation with connection ready for ground spike (not supplied)
Battery Switch (Optional)
- EXHAUST SYSTEM.
Maximum exhaust temperature: 502 ºC
Exhaust Gas Flow: 108 m3/min
Maximum allowed back pressure: 5,9 kPa
- NECESSARY AMOUNT OF AIR.
Intake air flow: 2700 m3/h
Cooling Air Flow: 14,33 m3/s
Alternator fan air flow: 1,46 m3/s
- STARTING SYSTEM.
Starting power: 7 kW
Starting power: 9,52 CV
Recommended battery: 200 x 2 Ah
Auxiliary Voltage: 24 Vdc
- FUEL SYSTEM
Fuel Oil Specifications: Diesel
Maximum power suction pump: 225 mm Hg
Maximum return feed pump: 450 mm Hg
Fuel Tank: 875 L
Dimensions
- DIMENSIONS.
Length: 4.200 mm
Height: 2.310 mm
Width: 1.600 mm
Maximum shipping volume: 15,52 m3
Weight with liquids in radiator and sump: 4.774 kg
Fuel tank capacity: 875 L
Autonomy: 7 Hours