HSY-20 T6

On-Site Power / HS RANGE

HSY-20 T6

Open Skid

Prime power22 kVA
Standby power26 kVA

TECHNICAL DATA

Specifications

Model code
G-1634-98-9-3
Engine
YANMAR
Alternator
MECC ALTE
Fuel
Diesel
Frequency
60 Hz
Phase
Three phase
Emissions
non certified
Version
Open Skid
Prime power
17.4 kW
Standby power
21 kW

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
480/277 V 60 Hz Three phase ECP28.M4C View PDF

INCLUDED

Equipment

Engine

Engine Specifications 1.800 r.p.m. Rated Engine Output: 19,6kW prp ; 23,3kW standby Manufacturer: YANMAR Model: 4TNV88HSPU Engine Type: 4-stroke diesel Injection Type: Direct Aspiration Type: Natural Number of cylinders and arrangement: 4-L Bore and Stroke: 88 x 90 mm Displacement: 2,19 L Cooling System: Coolant Lube Oil Specifications: SAE 3 class 10W30 / API grade CD,CF Compression Ratio: 19,1 Fuel Consumption ESP: 6,49 l/h Fuel Consumption 100% PRP: 5,38 l/h Fuel Consumption 75 % PRP: 4,10 l/h Fuel Consumption 50 % PRP: 3,00 l/h Lube oil consumption with full load: 0,27 Total oil capacity: 7,4 L Total coolant capacity: 5,5 L Governor Type Mechanical Air Filter Type Dry Inner diameter exhaust pipe: 51,6 mm Diesel engine 4-stroke cycle Water-cooled 12V electrical system Dry air filter Radiator with pusher fan Hot parts protection Moving parts protection

Alternator

Generator: MECC ALTE Model: ECP28.M4C Poles: 4 Connection type (standard): Star-series Mounting type: S-4 7,5" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Single bearing Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Chassis with integrated fuel tank Fuel level gauge Steel industrial silencer -15db(A) attenuation Manual oil drain pump (Optional) Fuel transfer pump (Optional) Steel residential silencer -35db(A) attenuation. (Optional)

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Adjustable earth leakage protection Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) Battery Switch (Optional) Optional Battery (Optima) (Optional) Leakage detector (Optional) - EXHAUST SYSTEM. Maximum exhaust temperature: 550 ÂșC Exhaust Gas Flow: 6,19 m3/min Maximum allowed back pressure: 1300 mm H2o - NECESSARY AMOUNT OF AIR. Intake air flow: 106,43 m3/h Cooling Air Flow: 0,987 m3/s Alternator fan air flow: 0,13 m3/s - STARTING SYSTEM. Starting power: 1,4 kW Starting power: 1,9 CV Recommended battery: 92 Ah Auxiliary Voltage: 12 Vdc - FUEL SYSTEM Fuel Oil Specifications: Diesel Fuel Tank: 60 L

Dimensions

- DIMENSIONS. Length: 1.450 mm Width: 620 mm Fuel tank capacity: 60 L Autonomy: 15 Hours