HGM-2030 T5 NG

Power Solutions / HP RANGE

HGM-2030 T5 NG

Open Skid

COP power2,028 kVA

TECHNICAL DATA

Specifications

Model code
G-1811-10-1-3
Engine
MTU
Alternator
STAMFORD
Fuel
Natural Gas
Frequency
50 Hz
Phase
Three phase
Emissions
non certified
Version
Open Skid

CONFIGURATION

Available voltages

VoltageFrequencyPhaseAlternatorDatasheet
400/230 V 50 Hz Three phase STAMFORD

INCLUDED

Equipment

Engine

Engine Specifications 1.500 r.p.m. Rated Engine Output: 2080kW cop Manufacturer: MTU Model: 16V4000L64.FNER Engine Type: 4-stroke Otto Cycle Injection Type: Carburization Aspiration Type: Turbocharged Number of cylinders and arrangement: 16-V Bore and Stroke: 170 x 210 mm Displacement: 76,3 L Cooling System: Water + Antifreeze Lube Oil Specifications: SAE 40 Compression Ratio: 12,5 Fuel Consumption 100% PRP: 4672 kW Fuel Consumption 75 % PRP: 3560 kW Fuel Consumption 50 % PRP: 2473 kW Total oil capacity: 330 L Governor Type Electrical Air Filter Type Dry Natural Gas engine 4-stroke cycle Water-cooled 24V electrical system Dry air filter Remote radiator HTW sender LOP sender Hot parts protection Moving parts protection

Alternator

Generator: STAMFORD Model: LV804T Poles: 4 Connection type (standard): Star Mounting type: S-00 21" Insulation: H class Enclosure (according IEC-34-5): IP23 Exciter system: Self-excited, brushless Voltage regulator: A.V.R. (Electronic) Bracket type: Double drive-shaft Coupling system: Flexible disc Coating type: Standard (Vacuum impregnation)

Version

- OPEN SET VERSION. Steel chassis Emergency stop button Anti-vibration shock absorbers Steel industrial silencer -15db(A) attenuation Steel residential silencer -35db(A) attenuation. (Optional) - GAS RAMP. Gas filter Double solenoid valve Gas pressure regulator Low pressure switch High pressure switch Inlet pressure manometer Outlet pressure manometer

Installation

- ELECTRICAL SYSTEM. Electric control and power panel with measurements devices and control unit (according to necessity and configuration) Battery Switch Battery charger (standard on gensets with automatic control panels) Heating resistor (standard on sets with automatic control panels) Battery charger alternator with ground connection Starter battery/ies installed (cables and bracket included) Ground connection electrical installation with connection ready for ground spike (not supplied) - EXHAUST SYSTEM. Maximum exhaust temperature: 421 ºC Exhaust Gas Flow: 121,4 m3/min Maximum allowed back pressure: 60 mbar - NECESSARY AMOUNT OF AIR. Intake air flow: 7754 m3/h Alternator fan air flow: 3,2 m3/s - STARTING SYSTEM. Starting power: 2 x 9 CV Auxiliary Voltage: 24 Vdc - FUEL SYSTEM Fuel Oil Specifications: Natural Gas

Dimensions

- DIMENSIONS. Length: 9.277 mm Height: 2.752 mm Width: 2.150 mm Maximum shipping volume: 54,89 m3 Weight with liquids in radiator and sump: 19.685 kg